Product Overview
AquaPlex-45 is XINKE LCS’s prefabricated liquid-cooled computing pod for high-density AI and high-performance computing (HPC). A standard 45-foot shipping container houses dedicated power, IT and cooling compartments, with integrated fire suppression and remote monitoring. The catalog configuration supports a total IT load of 280 kW. Deploy one pod as a standalone node or add pods as capacity needs grow.
Key Features
Factory assembly and testing
XINKE installs the wiring and piping and tests the integrated systems at the factory. On site, the pod is positioned, connected to power and the network, and checked before the IT load is brought online.
Combined air and liquid cooling
Direct-to-chip cold plates and rear-door cooling units handle heat from high-density servers. The pod can accommodate servers with NVIDIA B300 or GB300 GPUs, subject to project power, cooling and space requirements.
Dual power inputs and battery backup
A PC-class ATS switches automatically between two power sources. The UPS and lithium batteries provide 15 minutes at full load, allowing time to respond to a power event or shut down equipment in a controlled manner.
Controls and protection
PLC interlocks coordinate power and cooling, and the industrial IoT platform supports remote monitoring. Leak detection with location reporting, FD83 quick-connect couplings and clean agent fire suppression protect the pod.
Technical Specifications
| Parameter | Specification |
| Container format | 45-foot standard shipping container |
| Total IT load | 280 kW |
| Integrated cooling station capacity | 340 kW |
| CDU cooling capacity | 280 kW |
| CDU rated flow rate | 30 m³/h |
| Lithium battery backup runtime | 15 minutes at full load |
| Power source transfer | PC-class automatic transfer switch (ATS) for dual power feeds |
| Control system | System-wide PLC interlocking and industrial IoT cloud monitoring |
| Fire suppression | HFC-227ea clean agent fire suppression |
| Leak protection | Pod-wide leak detection with location reporting and FD83 leak-resistant quick-connect couplings |
| Annual PUE | ≤ 1.2 |
| Capacity per UPS unit | 400 kVA |
| Air-to-liquid cooling ratio | 2:8 |
| Cooling capacity per rear-door cooling unit | 15 kW |
How the System Works
Cold plates transfer chip heat to the coolant. A heat exchanger in the coolant distribution unit (CDU) transfers that heat to the facility-side circuit, and the integrated cooling station rejects it. Rear-door cooling units remove residual rack heat. The PLC coordinates power and cooling, and operators can monitor system status remotely.
Applications
AquaPlex-45 suits AI and HPC expansion, modular campus data centers, edge and remote sites, and temporary or emergency capacity. Single-pod and multi-pod deployments can be planned to suit site constraints and IT loads.