Prefabricated AI Data Center Pod (AquaPlex-45)

Product Overview

AquaPlex-45 is XINKE LCS’s prefabricated liquid-cooled computing pod for high-density AI and high-performance computing (HPC). A standard 45-foot shipping container houses dedicated power, IT and cooling compartments, with integrated fire suppression and remote monitoring. The catalog configuration supports a total IT load of 280 kW. Deploy one pod as a standalone node or add pods as capacity needs grow.

Key Features

Factory assembly and testing
XINKE installs the wiring and piping and tests the integrated systems at the factory. On site, the pod is positioned, connected to power and the network, and checked before the IT load is brought online.

Combined air and liquid cooling
Direct-to-chip cold plates and rear-door cooling units handle heat from high-density servers. The pod can accommodate servers with NVIDIA B300 or GB300 GPUs, subject to project power, cooling and space requirements.

Dual power inputs and battery backup
A PC-class ATS switches automatically between two power sources. The UPS and lithium batteries provide 15 minutes at full load, allowing time to respond to a power event or shut down equipment in a controlled manner.

Controls and protection
PLC interlocks coordinate power and cooling, and the industrial IoT platform supports remote monitoring. Leak detection with location reporting, FD83 quick-connect couplings and clean agent fire suppression protect the pod.

Technical Specifications

Parameter Specification
Container format 45-foot standard shipping container
Total IT load 280 kW
Integrated cooling station capacity 340 kW
CDU cooling capacity 280 kW
CDU rated flow rate 30 m³/h
Lithium battery backup runtime 15 minutes at full load
Power source transfer PC-class automatic transfer switch (ATS) for dual power feeds
Control system System-wide PLC interlocking and industrial IoT cloud monitoring
Fire suppression HFC-227ea clean agent fire suppression
Leak protection Pod-wide leak detection with location reporting and FD83 leak-resistant quick-connect couplings
Annual PUE ≤ 1.2
Capacity per UPS unit 400 kVA
Air-to-liquid cooling ratio 2:8
Cooling capacity per rear-door cooling unit 15 kW

How the System Works

Cold plates transfer chip heat to the coolant. A heat exchanger in the coolant distribution unit (CDU) transfers that heat to the facility-side circuit, and the integrated cooling station rejects it. Rear-door cooling units remove residual rack heat. The PLC coordinates power and cooling, and operators can monitor system status remotely.

Applications

AquaPlex-45 suits AI and HPC expansion, modular campus data centers, edge and remote sites, and temporary or emergency capacity. Single-pod and multi-pod deployments can be planned to suit site constraints and IT loads.

Project Inquiries

sales@xinkelcs.com • www.xinkelcs.com

Total IT Load Power
280
KW
Cooling Capacity of The IntegratedCooling Station
340
KW
CDU Cooling Capacity
280
KW
CDU Rated Flow Rate
30
m2/h
Lithium Battery Backup Duration
Full loadfor 15 minutes
Min
Power Supply Switching Method
ATS PC-Class Automatic Dual-Circuit Transfer Switch
Control System
PLC-based Comprehensive Interlocking + Industrial loT Cloud Monitoring
Fire Safety Plan
HFC-227ea Clean Agent Fire Suppression
Leakage Protection
Area-wide Pinpoint Leak Detection + FD83 Quick-connect Coupling for Physical Leak Prevention
Annual Total PUE Value
≤1.2
UPS Unit Capacity
400
kVA
Air-to-liquid Ratio
2:8
Cooling Capacity Per Rear-doorCooling Unit
15
KW