AvalonMiner 100-Position 20HQ Container Cooling Solution

100-position container cooling for AvalonMiner in 20HQ. Containerized mining with liquid cooling for Canaan ASIC farms.

Air + Liquid in One Box — 50 Air-Cooled + 50 2U Water-Cooled · Left/Right Independent Operation

Product Overview

The Avalon 20ft 100-Bay Hybrid Liquid Cooling Container is Xinke Intelligent’s hybrid containerized solution for Avalon-series mines, supporting a mixed configuration of 50 traditional air-cooled units and 50 2U water-cooled servers in a 20ft standard container, with the air-cooled and liquid-cooled zones co-located and operating independently on the left and right sides. One container carries both air-cooled and liquid-cooled equipment — the ideal vehicle for smoothly transitioning from air cooling to liquid cooling.

Pre-assembled and pre-commissioned at the factory, it goes live as soon as utilities are connected on site; the liquid-cooled zone uses a modular CDU architecture adapted to Avalon 2U water-cooled servers; core piping uses 304 stainless steel seamless pipe with water-electricity isolation and left/right independent operation for safety, stability and scheduling flexibility. With customized protection (IP54/IP55) for different climates, it is a high-value choice for hybrid deployment and progressive liquid cooling upgrades.

Key Features

01 Air + Liquid Hybrid, One Box, Two Uses: 100 bays support a mixed configuration of 50 traditional air-cooled + 50 2U water-cooled servers, with air-cooled and liquid-cooled equipment co-located in one box, accommodating both existing and new liquid-cooled equipment to lower the upgrade threshold.

02 Left/Right Independent Operation, Flexible Scheduling: The air-cooled and liquid-cooled zones operate independently on the left and right sides, allowing load-based scheduling where single-side maintenance does not affect the other — ensuring compute continuity and convenient O&M.

03 20ft Standard Container, Rapid Deployment: 20ft standard container, factory pre-assembled; goes live as soon as utilities are connected on site, drastically cutting construction time and fitting indoor and outdoor sites.

04 Modular CDU, 2U Water-Cooled Server Compatibility: The liquid-cooled zone uses a modular CDU architecture adapted to Avalon 2U water-cooled servers, supporting one-to-many combinations for larger liquid cooling deployment with fewer cooling units.

05 Water-Electricity Isolation Design, Safe Operation: Water and electrical circuits are physically isolated to eliminate cross-contamination safety hazards, protecting equipment and operators through high-intensity, long-duration operation.

06 304 Stainless Steel Seamless Piping, Clean & Contaminant-Free: Liquid-cooled core piping in 304 stainless steel seamless pipe keeps the system clean, corrosion-resistant and contaminant-free, with no scaling or leakage over time.

07 All-Climate Protection, Global Delivery: IP54/IP55-rated enclosure with anti-corrosion and anti-UV coating, customized for heat, severe cold, dryness and sandstorms — stable in different environments worldwide.

08 Smart Management, Full-Lifecycle Service: Optional XINKE SMART for remote monitoring, leak warning and energy analysis; 2-year warranty with 7×24 response and dedicated teams supporting overseas deployment.

Technical Specifications

Parameter Specification
Product Positioning 20ft hybrid liquid cooling container (for Avalon series · air + liquid)
Container Size 20ft standard container, indoor & outdoor
Bay Capacity 100 bays (50 traditional air-cooled + 50 2U water-cooled servers)
Hybrid Architecture Air-cooled + liquid-cooled zones co-located, left/right independent operation
Cooling Architecture Modular CDU (for Avalon 2U water-cooled servers)
Piping Material 304 stainless steel seamless piping (clean, corrosion-resistant)
Safety Design Water-electricity isolation, physically separated circuits
Protection Rating IP54 / IP55 (customizable)
Smart Management Optional XINKE SMART (unattended)
Deployment Form Factory pre-commissioned; go live on connection
Operating Environment Customized for heat, severe cold, dryness and sandstorms
Warranty 2 years, 7×24 service response

Note: Typical configuration parameters; the final specification is subject to the customized project solution.

 

Working Principle & System Positioning

The Avalon 20ft 100-Bay Hybrid Container runs with air and liquid zones working in concert: the air-cooled zone provides airflow cooling for traditional air-cooled equipment, while the liquid-cooled zone transfers 2U water-cooled server heat to the coolant via cold plates, delivered by the modular CDU through 304 stainless steel seamless piping to outdoor heat rejection terminals; the left and right sides operate independently without interference; water-electricity isolation ensures safety and the smart management system monitors both zones in real time. One container serves both air-cooled and liquid-cooled equipment, helping mines complete progressive liquid cooling upgrades while controlling investment.

Applications

  • Progressive upgrade from air cooling to liquid cooling for Avalon mines
  • Co-located deployment of traditional air-cooled and 2U water-cooled equipment
  • Rapid deployment and overseas rollout of mining farms
  • Low-cost hybrid computing for small-to-medium mining farms
  • Heat, severe-cold, dry and sandstorm regions

Services & Warranty

  • 2-year warranty with 7×24 service response
  • 365-day free on-site service in China, covering the full project lifecycle
  • Fully customizable: form factor, features, appearance and piping layout
  • Standard products delivered in 7-15 days; large custom projects in 30-45 days
  • Products delivered to 30+ countries and regions worldwide

Contact Us

Hotline: 400-106-2272

Email: sales@xinkelcs.com

External dimensions
L:6058mm、W:2438mm、H:2896mm
Internal dimensions
L:5860mm、W:2348mm、H:2720mm
Weight
3500KG
Installed capacity
100
Seat
Installed powerload
1000
KW
Power of the light-duty vertical multistage pump
18.5
KW
Power of the fluid replenishing pump
0.2
KW
Total power of the dry cooling tower fan
33.2
KW
Total power of the closed cooling tower fan
13.2
KW
Total power of the closed cooling tower spray pump
3
KW
System pipeline pressure
0.1-0.4
MPA
Operating temperature range of the system
0-50
Coolant circulation demand of a single machine
≥0.7
m³/h
Total demand for circulating coolant within the system
≥1.5
Molded Case Circuit Breaker
125
A
Residual Current Circuit Breaker
400
A
Contactor
9
A
Intermediate relay
24
V
CUL certified frequency converter
380
V
Price: