Antminer Water Cooled Servers 12-position cabinet cooling solution

Product description

This equipment is a 12-position dedicated cabinet designed for Antminer water-cooled servers, which is a special cabinet that integrates the position space, pumping station system and control system into one. It is equipped with CSA certification and CE certification to meet the rapid deployment requirements of global sites. The integration of the pumping station, control cabinet and machine position minimizes the space occupation and improves the transmission and heat transfer effect of coolant to the optimal level.

The standard configuration includes the XINKE SMART intelligent management system, enabling 24-hour unattended operation.

  1. The system can detect the power supply voltage and automatically shut down in case of overvoltage or undervoltage.
  1. Supports power and energy statistics, allowing users to view cumulative power consumption and real-time power usage.
  1. Visualized operating status, displaying real-time parameters such as pressure, temperature, and flow rate, with data storage and historical curve query functions for easy traceability and analysis.
  1. Equipped with constant pressure control function, automatically replenishing and depressurizing according to preset parameters to ensure stable system operation.
  1. The circulating pump supports dual modes: manual frequency setting or automatic frequency adjustment according to preset flow rate.
  1. Equipped with leak detection; immediately alarming and shutting down upon leak detection to prevent equipment damage and safety hazards.
  1. The server rack power supply uses a residual current circuit breaker, which automatically opens and closes according to the system operating status, providing reliable power supply protection.
External dimensions
L:900mm、W:1000mm、H:2000mm
Internal dimensions
L:850mm、W:920mm、H:1900mm
Weight
350KG
Installed capacity
12
PCS
Installed powerload
66
KW
Power of the light-duty vertical multistage pump
2.2
KW
Power of the fluid replenishing pump
0.2
KW
Total power of the dry cooling tower fan
4.15
KW
Total power of the closed cooling tower fan
0.55
KW
Total power of the closed cooling tower spray pump
0.75
KW
System pipeline pressure
0.2-0.4
MPA
Operating temperature range of the system
22-42
Coolant circulation demand of a single machine
≥0.5
m³/h
Total demand for circulating coolant within the system
≥0.12
Molded Case Circuit Breaker
160
A
Contactor
9
A
Intermediate relay
160
V
CUL certified frequency converter
380
V
Price: